Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM04335
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/11/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
| 10/09/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* | |
| 09/24/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) NEED REVISION ON PLANS APPROVED THRU PLAN CHECK FOR DELETION OF PANEL AND RECONFIGURED CIRCUITS TO EXIST PANEL. 2.) NEED APPROVAL FROM ARCH FOR USE OF MC CABLE IN LIEU OF RACE WAY PER PLAN. 3.) LIGHT FIXTURES TO HAVE 2 SCREWS EACH OPPOSITE ENDS. 4.) CONDUIT TO BE SUPPORTED WITHIN 3' EACH BOX AND AT 10' INTERVALS PER NEC. 5.) IF MC CABLE APPROVED USE LISTED STRAPS NOT 1/2" EMT STRAPS, ALSO WHERE RUN INSIDE CAVITY OF STUDS (METAL) MUST BE SECURED 1 1/4" FROM FACE TO PREVENT SCREWS FROM PENTRATING. 6.) DO NOT SUPPORT MC OR OTHER CONDUITS TO CONDUITS MUST BE SUPPORTED TO STRUCTURE. 110-3,300-4,334-10,300-11,348-13,334-10,99 NEC. |