Permit: T02CM04335

Parcel: 128150290

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T02CM04335

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/11/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
10/09/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*
09/24/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*1.) NEED REVISION ON PLANS APPROVED THRU PLAN CHECK FOR DELETION OF PANEL AND RECONFIGURED CIRCUITS TO EXIST PANEL. 2.) NEED APPROVAL FROM ARCH FOR USE OF MC CABLE IN LIEU OF RACE WAY PER PLAN. 3.) LIGHT FIXTURES TO HAVE 2 SCREWS EACH OPPOSITE ENDS. 4.) CONDUIT TO BE SUPPORTED WITHIN 3' EACH BOX AND AT 10' INTERVALS PER NEC. 5.) IF MC CABLE APPROVED USE LISTED STRAPS NOT 1/2" EMT STRAPS, ALSO WHERE RUN INSIDE CAVITY OF STUDS (METAL) MUST BE SECURED 1 1/4" FROM FACE TO PREVENT SCREWS FROM PENTRATING. 6.) DO NOT SUPPORT MC OR OTHER CONDUITS TO CONDUITS MUST BE SUPPORTED TO STRUCTURE. 110-3,300-4,334-10,300-11,348-13,334-10,99 NEC.