Permit: T02CM04335

Parcel: 128150290

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM04335

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/11/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
10/09/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*NEED WRITTEN APPROVAL BY ARCHITECT/ENGINEER OF RECORD APPROVING THE USE OF MC CABLE. 2.) NEED WRITTEN APPROVAL BY ATCHITECT/ENGINEER OF RECORD ALLOWING THE USE OF TWO WIRE MC WITHOUT THE INSULATED GREEN GROUNDING CONDUCTOR SPECIFIED ON NOTE 5 OF THE ELECTRICAL SPECS ON PLAN SHEET E2.
09/24/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*