Permit: T02CM04322

Parcel: 11712019A


Addresses:

51 N 6TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/01/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
09/30/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) CONCENTRICS ARE SEPERATING AT PANEL "C' CONDUIT IS BEING USED AS A GROUND. PLEASE INSTALL REDUCING WASERS AND BONDING BUSHING TO MAINTAIN GROUNDING & BONDING.2.) WE HAVE MUTIPOLE TERMANATION AT PANEL "B" 3.) PLEASE USE CORRECT COLOR CODEING AS PER CITY/ADMENDMENTS FOR UNGROUNDING CONDUCTORS 4.) CANNOT USE SHEET METAL SCREWS FOR GROUNDING AND CLEAN SURFACE UNDERGROUND BAR. 5.) FILL UNUSED OPENING AT PANEL AT "A" 6.) BOND DISCONNECT ENCLOUSER MAIN DISCONNECT.