Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/01/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 09/30/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) CONCENTRICS ARE SEPERATING AT PANEL "C' CONDUIT IS BEING USED AS A GROUND. PLEASE INSTALL REDUCING WASERS AND BONDING BUSHING TO MAINTAIN GROUNDING & BONDING.2.) WE HAVE MUTIPOLE TERMANATION AT PANEL "B" 3.) PLEASE USE CORRECT COLOR CODEING AS PER CITY/ADMENDMENTS FOR UNGROUNDING CONDUCTORS 4.) CANNOT USE SHEET METAL SCREWS FOR GROUNDING AND CLEAN SURFACE UNDERGROUND BAR. 5.) FILL UNUSED OPENING AT PANEL AT "A" 6.) BOND DISCONNECT ENCLOUSER MAIN DISCONNECT. |