Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/05/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. OK FOR C OF O. |
| 10/23/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 50 AMP CIRCUIT BREAKERS ARE TOO LARGE FOR A/C EQUIPMENT. 45 AMP IS MAX FUSE OR HACK BREAKER. NEED TO SEE CO2 CENSORS WORK CORRECTLY. RECALL FOR INSPECTION. |