Permit: T02CM04316

Parcel: 12617228A

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
08/12/2003 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) OK FOR SHEET ROCK
08/01/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) CHECKED CONDENSATE DRAINS, SUSPENDED ROUGH DUCT. FINISH SEALING DUCT CONNECTIONS. DUCT SMOKE DETECTORS TO BE INSTALLED IN THE RETURN PLENUMNS. PROVIDE ACCESS. PENETRATIONS THRU FIRE WALLS ARE REQUIRED TO HAVE FIRE DAMPERS. PROVIDE REVISION TO PLANS SHOWING LOCATION, SIZE, TYPE, ETC...