Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/21/2003 |
SHEET ROCK NAILING |
|
Approved |
IVRS - Inspection 0000* |
| 08/20/2003 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* PENETRATIONS IN NORTH UNI-SEX REQUIRE FIRE STOP |
| 08/11/2003 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* ABOVE CEILING FIRE STOP NORTH BATH OK |
| 08/08/2003 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* 10 DO NOT TAPE AROUND ANY FIRE BARRIER PENETRATIONS UNTIL i HAVE INSPTED FIRE STOP APPLICATION. 2)REAPPLY FIRE STOP COMPOUND AROUND DUCT PENETRATING NORTH WALL, IT HAS NOT BEEN APPLIED TO FULL 5/8 DEPTH OF GYPBOEARD. 3) OK TO TAPE EXCEPT FOR AREAS NOTED ABOVE. |