Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM04304
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
12/05/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) FINISH ELECTRIC IN WALK IN BOX & SEAL INSIDE OF CONDUIT FROM AN BOX ENTRANCE. 2.) A DISCONNECTING MEANS IS NEEDED FOR ICE MACHINE. 3.) PLANS CALL FOR 250 KCMIL TO PANEL "A: WE HAVE 3/0 RUN. 4.) FINISH #4,5,9,10,12, PREVIOUS INSPECTION |
|
12/04/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) WE HAVE LOOSE FITTINGS IN WALK IN BOX CONDUIT & SEALTITE. 2.) SUPPORT SEALTITE AS PER CODE & CONDUIT FOR WALK IN BOX. 3.) SMALL SODA DISPENSER NEED LISTING LABEL. 4.) SEAL CONDUITS ENTERING WALK IN BOX. 5.) SUPPORT FLEX TO WATER HEATER AND PREVENT DIELECTRIC CONTACT 6.) PLEASE VERIFY THAT EXISTING PANEL "A" IS MADE BY CUTLER HAMMER. 7.) BREAKERS DO NOT MATCH PANEL SCHEDULE FOR AMPACITY. 8.) WHERE IS ICE MACHINE ON PLANS? AND DISCONNECTING MEANS 9.) SUPPORT FLEX FOR OVEN AND TIGHTEN LOOSE FITTINGS. |
|
12/03/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*EXTENDER RING ARE NEEDED FOR BOXES WHERE MORE THAN 1/4" FROM 2.) FINISH WALK IN BOXES ALSO SEAL ENTRANCES TO BOX. 3.) FINISH ELECTRIC. |