Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/05/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 12/04/2002 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 12/03/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) INSTALL NUT ON FRONT RIGHT GARAGE A.B. 2) REPAIR FIRE BLOCK AT GARAGE TO HOUSE DOOR AND LAUNDRY WALL 3) NEED DWV TEST 4) BANG PLATE CONDENSATE LINE, KITCHEN VENT PIPE 5) FINISH H.D. INSTALL 6) GROUND MASTER BATH PANCAKE BOX 7) SHIM MASTER NORTH WINDOW HEADER 8) CORRECT DRYER VENT LENGTH 9) CONNECT SECONDARY CONDENSATE LINE |
| 11/29/2002 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 11/25/2002 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |