Permit: T02CM04244

Parcel: 13405116C


Addresses:

990 S HARRISON RD


Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T02CM04244

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
03/26/2003 MECHANICAL - HOODS Approved IVRS - Inspection 0000*CHECKED FIRE WRAP & HOOD INSTALLATION.
03/20/2003 MECHANICAL - HOODS Partial Approval IVRS - Inspection 0000*FIRE WRAP MUST EXTEND ALL THE WAY TO THE TOP OF THE DUCT. SEE SECTION 506.3.11 EXCEPTION 1 2000 IMC
RECALL FOR INSPECTION.