Permit: T02CM04244

Parcel: 13405116C


Addresses:

990 S HARRISON RD


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T02CM04244

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/26/2003 MECHANICAL - INTERMEDIATE Approved
03/17/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) PROVIDE BACKING AROUND CEILING BOXES IN RESTROOMS. STRAP BATHROOM EXHAUST DUCT TO ROOF JOISTS. OK FOR SHEET ROCK.
2.) CHECKED CONDENSATE DRAIN LINE IN WALL. EXTEND 90 ELL TO DRIP INTO MOP SINK PROVIDE DRAIN FROM EVAP COOLER.
3.) PROVIDE DUCT SMOKE DETECTORS. WILL CHECK ON ABOVE CEILING INSPECTION.
4.) INSPECTED GREASE DUCTS. & WELDS OK TO PROCEED W/SHAFTS. IF USING FIRE WRAP, PROVIDE A REVISION FROM YOUR DESIGNERS.