Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T02CM04244
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/26/2003 | MECHANICAL - INTERMEDIATE | Approved | ||
03/17/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) PROVIDE BACKING AROUND CEILING BOXES IN RESTROOMS. STRAP BATHROOM EXHAUST DUCT TO ROOF JOISTS. OK FOR SHEET ROCK. 2.) CHECKED CONDENSATE DRAIN LINE IN WALL. EXTEND 90 ELL TO DRIP INTO MOP SINK PROVIDE DRAIN FROM EVAP COOLER. 3.) PROVIDE DUCT SMOKE DETECTORS. WILL CHECK ON ABOVE CEILING INSPECTION. 4.) INSPECTED GREASE DUCTS. & WELDS OK TO PROCEED W/SHAFTS. IF USING FIRE WRAP, PROVIDE A REVISION FROM YOUR DESIGNERS. |