Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T02CM04244
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/26/2003 | PLUMBING - INTERMEDIATE | Approved | ||
03/31/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1.) SEE NOTE #4 FROM 032003 AND COMPLY, ALSO ROOF DRAINS ARE GRAVITY FLOW, CORRECT BACKPITCHED SECTIONS AND RETEST. 2.) 2" WASTE LINE UNDER SLAB, REPAIRED OK OK TO COVER. |
|
03/26/2003 | PLUMBING - INTERMEDIATE | Denied | DO NOT CALL FOR INSPECTION UNTIL YOU ARE READY | |
03/20/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1.) SOIL WATER TEST FOR WASTE & VENT SYSTEM ABOVE FLOOR IS OK 2.) GAS PRESSURE TEST FROM 3" TO 2 1/2" ANZUL VALVE LOCATION & GAS LINES FOR AC UNITS IS OK 3.) NOTE: MUST LOCATE AND REPAIR LEAK OR BROKEN WASTE LINE UNDER SLAB. 4.) MUST EXPOSE OVERFLOW DRAIN IN WALL AND REPLACE SECTION AND RETEST SYSTEM. |
|
03/18/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*NOT READY FOR INSPECTION. | |
03/17/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*MUST PROVIDE WATER TEST ON WASTE & VENT SYSTEM 2.) NO TEST ON GAS. |