Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T02CM04244
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2003 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection 0000* | |
01/22/2003 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000*18' | |
01/21/2003 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000*/ 1) PARTIAL 18' | |
01/16/2003 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000* | |
01/14/2003 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000*9'4" E,S,N; 12' AFFE N. | |
01/13/2003 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection 0000*1.) SOUTH, EAST & WEST 4' 8' AFF. 2.) JAMB REINFORCING AT REAR DOORS NOT INSTALLED PER ENGIEERS REPAIR, PLEASE PROVIDE NEW FIX. |
|
01/10/2003 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection 0999*1.) PLEASE SEE 11/5.4 FOD JAMB REQUIREMENT AT REAR DOORS. YOU ARE MISSING THE 4 EA #5' AND BEA #5' AT JAMBS. 2.) LAP SPLICE LENGTH OF 24" OUT OF STEM WALL IS NOT SUFFICIENT PER EQUATION 21-25 OF IBC. 3.) PROVIDE ENGINEER APPROVED REPAIR FOR ABOVE. 4.) ALL SPECIAL INSPECTION REPORTS ARE TO BE ON SITE. |