Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM04201
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/05/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
11/04/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) PROVIDE CLIPS FROM TRUSS CHORD TO DOUBLE TOP PLATE AT REAR EXTERIOR SHEARWALL PER SCHEDULE ON DT/10 SHEARWALL 5 EACH 16" 2) GARAGE SHEARWALL REQUIRES CLIPS FROM TRUSS TO TOP PLATE EACH 12" PER SHEARWALL 6 DT1/10 3) ADDITIONAL STRAP ON GAS PIPING IN DINING ROOM RUN OF 15' 4) TIGHTEN ANCHOR BOLTS MARKED WITH RED X ALSO HOLDOWN IN LAUNDRY ROOM. RED X 5) A/C DUCT BEDROOM NOT BLOCKED ON 3 SIDES |