Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/05/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/04/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE CLIPS FROM TRUSS CHORD TO DOUBLE TOP PLATE AT REAR EXTERIOR SHEARWALL PER SCHEDULE ON DT/10 SHEARWALL 5 EACH 16" 2) GARAGE SHEARWALL REQUIRES CLIPS FROM TRUSS TO TOP PLATE EACH 12" PER SHEARWALL 6 DT1/10 3) ADDITIONAL STRAP ON GAS PIPING IN DINING ROOM RUN OF 15' 4) TIGHTEN ANCHOR BOLTS MARKED WITH RED X ALSO HOLDOWN IN LAUNDRY ROOM. RED X 5) A/C DUCT BEDROOM NOT BLOCKED ON 3 SIDES |