Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/24/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 12/23/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED DWV TEST 2) BANG PLATE HALL BATH SINK VENT IN ADJOINING CLOSET |
| 12/19/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) SEE PREVIOUS INSPECTION LIST |
| 12/17/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) REPLACE FIREBLOCK WEST OF GARAGE/HOUSE DOOR 2) BANG PLATE KITCHEN SINK VENT AT TOP 3) SECURE 4 GANG BOX 4) SHIM HEADERS WHERE NEEDED 5) CONDENSATE LINES NOT IN 6) NEED DWV AND WATERTEST 7) FINISH HALL TUB DRAIN INSTALLATION AND GROUT 8) BANG PLATE HALL BATH SINK VENT IN ADJOINING CLOSET |