Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2003 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*/ 1) OK TO TILE |
| 09/26/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK EXIT AND AND EMERGENCY LIGHTING SALES FLOOR CORRIDOR #2, OFFICE, 1-HOUR PHOTO ABOVE CEILING |
| 09/22/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK STRIP LIGHTING AND CONDUITS 2) INSTALL EMG AND EXIT LIGHTING 3) FINISH DUCT DETECTORS 4) OK TO TILE SALES FLOOR EXCEPT AS NOTED 5) OK ROOF UNITS 6) RECEIVED PAPERWORK FOR TORQUE AND LOCKOUT/TAG OUT |
| 09/19/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK TEMP POWER FOR TEST 2) PLEASE PROVIDE LETTER FOR TORQUE AND LOCK OUT/TAG OUT PROCEDURES |