Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* RECEIVED LETTER FOR FIXTURE AND PANEL |
|
| 11/07/2002 | ELECTRIC - ABOVE CEILING | Denied | 1)PLEASE SUPPORT JUNCTION BOX TO STRUCTURE 2)SUPPORTM/C CABLE AS PER CODE 12"FROM BOX OR FITTING AND EVERY 6' AFTER. 3)FILL UNUSED OPENINGS IN JUNCTION BOXES AND INSTALL MISSING COVER PLATES. 4)FIXTURES TO BE SUPORRTED ON OPPISITE CORNERS AND HAVE ALL WIRES ATTACHED TO FIXTURES-2 PER FIXTURE. 5)PLEASE PROVIDE A LETTER FROM ARCHITECT AUTHURIZING USE OF OLD FIXTURES. PLANS CALL FOR NEW. ALSO PANELS "A" & "B" |