Permit: T02CM04186

Parcel: 11306142F

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/13/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
RECEIVED LETTER FOR FIXTURE AND PANEL
11/07/2002 ELECTRIC - ABOVE CEILING Denied 1)PLEASE SUPPORT JUNCTION BOX TO STRUCTURE
2)SUPPORTM/C CABLE AS PER CODE 12"FROM BOX OR FITTING AND EVERY 6' AFTER.
3)FILL UNUSED OPENINGS IN JUNCTION BOXES AND INSTALL MISSING COVER PLATES.
4)FIXTURES TO BE SUPORRTED ON OPPISITE CORNERS AND HAVE ALL WIRES ATTACHED TO FIXTURES-2 PER FIXTURE.
5)PLEASE PROVIDE A LETTER FROM ARCHITECT AUTHURIZING USE OF OLD FIXTURES. PLANS CALL FOR NEW. ALSO PANELS "A" & "B"