Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/22/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS LINE NOT SECURED OR PROTECTED-PLAN CALLS FOR BLACK PIPE 2) INSTALL CLEANOUT FOOT VENT CHI-LOOP 3) TAPE OFF BARE ENDS OF ELECTRIC CONDUCTORS MAIN PANEL 4) GROUND NOT GFCI/CONNECTED 5) SECURE LINE WIRES AWAY FROM HOT PARTS 6) FIREPLACE NOT INSTALLED |
|
| 03/15/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NEED NOTES FROM ARCHITECT, REF FIREPLACE COMBUSTIBLE MATERIAL CLOSER THAN 2" 2) BANG PLATES ON PIPES AND WIRES 3) ZERO CLEARANCE FIREPLACE TO BE INSTALLED IN NORTH MASTER BEDROOM 4) DIVERTER STUD NOTCHED TO DEEP MASTER SHOWER 5) RUN WIRES THRU, WALL FOR PORCH LIGHTS 6) CONNECT SMOKE DETECTORS S/W GREAT ROOM 7) STIFF LEG CEILING 2 X 4 AT FRONT OFFICE WEST 8) RUN CONDENSATE THRU WALL 9) PEX 12" AWAY FROM LIGHT CANS SOUTH HALL AND KITCHEN 10) CLEANOUT FOR FOOT VENT CHI/LOOP 11) CHECK HEADER SIZE 2ND FLOOR BELOW GIRDER 12) FINISH GAS LINE, NEED PRESSURE TEST 13) H20 HTR NEEDS DIRECT VENT 14) H20 PRESS-OK, DWV TEST OK |
|
| 03/11/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE ALL REVISIONS, SEE INSPECTION DATED 11/17/04 2) ELECTRICAL NOT COMPLETE 3) LEAK AT LAUNDRY 4) NO TEST ON DWV'S |