Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/18/2003 |
FRAMING |
|
Approved |
|
| 06/10/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) WHAT HAPPENED TO 4 X 4 ELECTRIC BOX INTO EAST LAUNDRY ? |
| 06/06/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FIRE STOP AROUND ANY ELECTRIC BOXES LESS THAN 7" SEPARATION HORIZONTAL 2) OK TO ROCK ELSEWHERE |
| 06/04/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) SEE #5 FROM 5/28/03 2) SEE #1 FROM 5/28/03 3) ELECTRIC BOXES IN FIREWALL LESS THAN 7" HORIZONTALLY MUST HAVE PULLY PADS OR OTHER FIRE SAFETY OR PROVIDE LISTIN SHOWING THEY MAY BE CLOSER 4) PROVIDE A CONTAINER OF THE TOAM PRODUCT YOU USED IN FIRE WALL TO SEAL SMALL HOLES 5) PROVIDE APPROVED PLUMBING INTERMEDIATE 6) NAIL PLATES REQUIRED TO PROTECT ABS PLUMBING LESS THATN 1 1/4" FROM WALL FACE 7) I WILL CHARGE A REINSPECTION FEE IF THESE ITEMS ARE NOT READY IN THE FUTURE |
| 05/30/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |
| 05/28/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) OVER NOTCHED STUDS AT FIRE WALL 2) PROVIDE 1-HR LISTED WASHER BOXES FOR BACK TO BACK INSTALLATION IN FIREWALL 3) FIRE WALL MUST BE COMPLETED BEHIND TUBS BEFORE THEY ARE INSTALLED 4) REFRIGERATOR WATER SUPPLY BOXES MUST BE ONE HOUR RATED 5) STUDS IN PLUMBING WALLS MUST CONTINUE TO BOTTOM PLATE |