Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM04164
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/29/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
04/28/2003 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) ADD STUDS WHERE TOP PLATES ARE NOT SPLICED OVER STUDS 2) BLOCK DUCT 3 SIDES BATH 3) ADD RED HEADS (1/2") 12" FROM PLATE EDGE MAXIMUM 4) COMPLETE DUCT INSTALLATION 5) FIRE STOP AT DOUBLE TOP PLATE AT REF-LINE 6) CROSS BRACE TRUSSES AT EACH END AND 25 FEET ON CENTER MAXIMUM 7) CAULK ALL PENETRATIONS AT MESH 8) STOPPED INSPECTION, HAVE (SUPER) CHECK SITE AND RECALL |