Permit: T02CM04156

Parcel: 110065540

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T02CM04156

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
12/03/2002 FRAMING Approved IVRS - Inspection 0000*
11/05/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) POST TENSION FLOOR CRACKED SLAB CRACKED IN MORE THAN 10 PLACES. PROVIDE CITY OF TUCSON APPROVED ENGINEERS EVALUATION AND REPORT 2) REVISE PLAN FOR DELEATED WINDOWS AND PROVIDE LITE VENT CALCULATIONS APPROVED BY CITY OF TUCSON 3) PROVIDE PROOF THAT TOILET OFFSET FLANGE IS UPC LISTED 4) DO NOT INSULATE OR DRYWALL
10/28/2002 FRAMING Denied IVRS - Inspection 0950*/ 1) CANNOT APPROVE/INSPECT INTERMEDIATE ITEMS UNTIL HOUSE IS LATHED AND APPROVED 2) PEX OUTSIDE OF WALL CAVITY 3) REVISE PLAN FOR TWO DELETED 3040 WINDOWS IN LIVING ROOM PROVIDE NATURAL LIGHT CALCULATIONS 4) LOST 1/2 PSI ON GAS TEST IN 15 MINUTES 5) FIREBLOCKS MISSING WEST WALL 6) ANCHOR BOLTS MISSING ON BEARING WALL 7) TRUSSES NOT CLIPPED AT INTERIOR BEARING WALL 12/D1 8) STOPPED INSPECTION