Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/19/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FOR C OF O. |
| 12/18/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*DUCT SMOKE DETECTORS NOT INSTALLED PER SPECS. |
| 12/17/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PROVIDE MORE BONDING ON GREASE DUCT WRAP. MUST BE SPACED MAX. 10 1/2" PROVIDE PINS ON AREAS WHERE BANDS WONT WORK. RECALL FOR INSPECTION. |
| 12/10/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PROVIDE CLEAN OUTS ON GREASE DUCTS AS PER MANUFACTUERS INSTRUCTIONS OK TO PROCEED W/FIRE WRAP. OK FOR PARTIAL CEILING TILES. TUBES ON SMOKE DETECTORS NOT LONG ENOUGH. |