Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/08/2002 |
BUILDING ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*SUBJECT TO DETAIL A SHEET E-3 INSTALL PER DETAIL. |
| 11/07/2002 |
BUILDING ABOVE CEILING |
|
Denied |
IVRS - Inspection 0920*NO ACCESS. |
| 10/11/2002 |
BUILDING ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) PLEASE NOTE THAT CEILING GRID REQUIRES SUSPENSION WIRES 8" OR LESS FROM PERIMETER WALLS. 2.) PLEASE PROVIDE RFI FROM ARCHITECT OF RECORD DELETING DETAIL A PAGE A-3 OR INSTALL SEISMIC CEILING SYSTEM PER DETAIL. |