Permit: T02CM04107

Parcel: 107040180

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/13/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
OK FINAL STOI.
11/12/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) PLEASE CLEAN SURFACE UNDER GROUND LUGS.
2.) VERIFY LISTED RANGE FOR CONDUCTOR IN MULTI TAP IN GUTTER.
3.) BONDING DEVICES ARE NEEDED ON BOTH SIDES OF 250-94. NIPPLES UNTIL THE 1ST DISCONNECTING
FUSES.
4.) PLEASE VERIFY FROM ENGINEER IF 3/0 FOR SERVICE IS OK. HAVE HIM PROVIDE A LETTER IF OR OK INSTALL AS PER PLANS.