Permit: T02CM04107

Parcel: 107040180

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/15/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*OK WALLS AND HARD CEILINGS.
10/14/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) USE AN APPROVED FITTING AT L.B. CHASE NIPPLE NO APPROVED EXTEND JUNCTION BOX OUT TO WHERE DRYWALL SURFACE TO BE. 3.) TIGHTEN LOOSE FITTINGS SET SCREWS AND LOCKNUTS. 4.) SUPPORT M/C CABLE WITHIN 12" OF BOXES 5.) MISSING PLASTER RINGS. 6.) PLEASE PROVIDE A LETTER AUTHURIZING USE OF M/C CABLE OR INSTALL AS PER PLANS.