Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/15/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*OK WALLS AND HARD CEILINGS. |
| 10/14/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) USE AN APPROVED FITTING AT L.B. CHASE NIPPLE NO APPROVED EXTEND JUNCTION BOX OUT TO WHERE DRYWALL SURFACE TO BE. 3.) TIGHTEN LOOSE FITTINGS SET SCREWS AND LOCKNUTS. 4.) SUPPORT M/C CABLE WITHIN 12" OF BOXES 5.) MISSING PLASTER RINGS. 6.) PLEASE PROVIDE A LETTER AUTHURIZING USE OF M/C CABLE OR INSTALL AS PER PLANS. |