Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/04/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/22/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0950*/ 1) CANNOT APPROVE INTEMEDIATE ITEMS UNTIL EXTERIOR OF BUILDING IS LATHED 2) NAIL PROTECT ALL WIRES AND PLUMBING WITHIN 1 1/4" OF STUD SURFACES 3) DRAFT STOP FURNACE PLATFORM 4) PROVIDE PLUMBING DWV WATER TEST PER UPC SECTION 712.2 5) ALL WIRES MUST TERMINATE IN APPROVED ELECTRIC BOXES 6) EDGE NAILING OF WIRES NOT ALLOWED 7) NO OTHER OUTLETS ALLOWED ON BATHROOM GFCI CIRCUIT 8) SECURE ALL ROMEX CLAMPS 9) BEDROOM AND ROOM LEADING TO BEDROOM REQUIRE SMOKE DETECTORS |