Permit: T02CM04065

Parcel: 113043250

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/23/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
12/13/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*CANNOT TERMINATE CONDENSATE DRAIN INTO
1.) ROOF TOP WET SEWER VENT. RUN ACCROSS ROOF, DOWN TO SOIL IN PVC. OR ROOF GUTTER W/DOWN SPOUT.
2.) PROVIDE FILTERED OUTSIDE AIR VENT, AS PER IMC 2000, IN RETURN AIR DUCT. OK FOR GAS CLEARANCE CARD.