Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* 1.) CORRECTION MADE OK 2.) PLUMBING FINAL OK 3.) OK FOR C OF O PENDING ANY OTHER INSPECTIONS. |
|
| 01/06/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1.) CLEAN OUTS REQUIRE 12" CLEARANCE IN FRONT OF CLEAN OUT. 2.) RAISED HEAD PLUG PRESENTS TRIPPING HAZARD AT 2 WAY CLEANOUT 3.) WATER HEATER ENCLOSURE NOT COMPLETE 4.) NO T & P RELIEF DRAIN ON WATER HEATERS. 5.) ALL HOSE BIBB REQUIRE VACUUM BREAKERS.DEVELOPMENT SERVICE 791-5550 147 S. LONG. |