Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM04061
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/18/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
10/17/2002 | FRAMING | Denied | IVRS - Inspection 0999* DIAGONAL BRACE ON S. END, W. SIDE OF VENT IS NOT PROPERLY CUT AND EITHER AT TOP | |
10/16/2002 | FRAMING | Denied | 1) REMOVE, RECUT AND INSTALL GABLE END DIAGONAL BRACING PER DETAIL DT1/6, BRACE TO 2ND TRUSS WITH BLOCKING SPECIFIED 2) NEED WATER TEST ON DRAIN AND VENT PIPING 3) MECHANICAL DUCTING NOT COMPLETE IN GARAGE AND ABOVE ENTRY HALLWAY |