Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/03/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FINISH WATER HEATER 2) APPROVED EXTENDER RINGS ARE NEEDED FOR BOXES MORE THAN 1/4" IN NON COMBUSTIBLE AND FLUSH IN COMBUSTIBLES METAL NOT APPROVED 370.20 3) FILL UNUSED OPENINGS IN BOXES 4) CANNOT TRIM CONDUCTOR STRANDS AT MAIN BREAKER 5) PLEASE CLEAN SURFACE UNDER LUGS FOR GROUNDING 6) PROTECT SEAL TITE FROM SHARP METAL EDGES 7) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 8) SUPPORT CONDUIT SUPPORTS 9) NOTE: HAVE BLDG INSPECTOR CHECK FIRE PENETRATIONS |