Inspection History: ELECTRIC - FINAL

Permit Number - T02CM04056

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/19/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/03/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) FINISH WATER HEATER 2) APPROVED EXTENDER RINGS ARE NEEDED FOR BOXES MORE THAN 1/4" IN NON COMBUSTIBLE AND FLUSH IN COMBUSTIBLES METAL NOT APPROVED 370.20 3) FILL UNUSED OPENINGS IN BOXES 4) CANNOT TRIM CONDUCTOR STRANDS AT MAIN BREAKER 5) PLEASE CLEAN SURFACE UNDER LUGS FOR GROUNDING 6) PROTECT SEAL TITE FROM SHARP METAL EDGES 7) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 8) SUPPORT CONDUIT SUPPORTS 9) NOTE: HAVE BLDG INSPECTOR CHECK FIRE PENETRATIONS