Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM04056
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/03/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) FINISH WATER HEATER 2) APPROVED EXTENDER RINGS ARE NEEDED FOR BOXES MORE THAN 1/4" IN NON COMBUSTIBLE AND FLUSH IN COMBUSTIBLES METAL NOT APPROVED 370.20 3) FILL UNUSED OPENINGS IN BOXES 4) CANNOT TRIM CONDUCTOR STRANDS AT MAIN BREAKER 5) PLEASE CLEAN SURFACE UNDER LUGS FOR GROUNDING 6) PROTECT SEAL TITE FROM SHARP METAL EDGES 7) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 8) SUPPORT CONDUIT SUPPORTS 9) NOTE: HAVE BLDG INSPECTOR CHECK FIRE PENETRATIONS |