Permit: T02CM04054

Parcel: 128090030

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
07/09/2003 PLUMBING - INTERMEDIATE Approved 1) SOIL WATER TEST IS OK 2) POC OF NEW BLDG DRAINS TO EXISTING BLDG DRAINS IS OK 3) OK TO BACKFILL TRENCH 4) OK FOR DRYWALL
07/01/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) SPECS CALL FOR HUSKEY BANDS BELOW SLAB 2) MUST PROVIDE A 10' HEAD OF WATER TEST ON WASTE 3) MUST ROUGH FS1 IN A CONVENTION MANNER FLAT VENT SYSTEM IS ACCEPTED ONLY IF A STRUCTURE CONDITION IS PRESENT 4) MUST PROVIDE INSULATORS WHERE ANY COPPER WATER LINE PENETRATE THROUGH METAL STUBS
04/30/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OVERHEAD WATER DISTRIBUTION IS OK IN KITCHEN ADDITION.
2.) OK TO DRYWALL.