Permit: T02CM04041

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T02CM04041

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
03/17/2003 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK
2.) NOTE: BLDG. DRAIN IS STUBBED OUT @ TWO WAY C.O. ONLY.
3.) OK TO BACKFILL TRENCH.
03/14/2003 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) PIPE IS TO BE LAID ON A FIRM BED NO BRIDGING ALLOWED.
2.) MINIMUM 2 PIPE DIAMETERS FROM WEIR OF TRAP TO POINT OF VENT OTHERWISE YOU HAVE AN "5" TRAP.
3.) FIGURE FIVE MAY NOT LAY ON ITS SIDE.
4.) REQUIRED 2% PITCH ON BLDG DRAIN.