Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM04041
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
06/26/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ 1) BEDROOMS NOT CIRCUITED PER PLAN, ALSO NEEDS TO BE ON ARC-FAULT BREAKERS PER '99-2002 NEC 2) PLAN CALL FOR LOCKABLE BREAKERS FOR WATER HEATERS 3) PROVIDE LETTER FROM ARCH. VERIFYING DELETION OF WASHER/DRYER HOOK UP FOR POWER |