Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM04040
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
06/26/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ 1) BEDROOMS NOT CIRCUITED PER PLAN. ALSO NEED TO BE ON ARC FAULT CIRCUIT BREAKERS PER '99-2002 NEC 2) PLAN CALLS FOR LOCKABLE BREAKERS FOR WATER 3) PROVIDE LETTER FROM ARCH HEATERS VERIFYING DELETION OF WASHER/DRYER HOOKUPS FOR POWER |