Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/16/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ OK FOR C OF O. LEFT GAS CARD. |
| 12/15/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ NEED TO SEE DUCT SMOKE DETECTORS POWERED UP. |
| 12/11/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ DUCT SMOKE DETECTOR FOR A/C - 7 IS INSTALLED OK. STILL NEED TO SEE POWERED UP. DUCT SMOKE DETECTOR FOR A/C - 8 INSTALLED IN WRONG LOCATION. MUST BE UPSTREAM OF ALL INLETS. CANNOT CONFIRM PROPER FUSING AT UNITS UNTIL ROOF COATING IS DRY. |
| 12/08/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ PROVIDE FUSES IN ELEC. DISCONNECTS AS PER DATA PLATES. PROVIDE DUCT SMOKE DETECTORS AS PER PLANS. RE-CALL FOR INSPECTION. |