Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T02CM04035
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2003 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000*/ NEED TO SEE DUCT SMOKE DETECTOR, UNIT 8. PROVIDE MIN. 1" CLEARANCE FROM INSULATION AND COMBUSTABLES AROUND WATER HEATER VENT. PROVIDE AN EXPLANATION FROM YOUR ENGINEER WHY AC-7 HAS A DUCT SMOKE DETECTOR AND WHY IT IS IN THE SUPPLY DUCT. COMBUSTION AIR DUCTS IN WATER HEATER ROOM MUST BE SEPERATE UNTIL THEY GET TO THE ROOF. LEAVE OUT CEILING TILES IN AREAS TO BE REINSPECTED. WILL CHECK CORRECTIONS ON FINAL. | |
10/14/2003 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ INSPECTED SUPPLY AND EXHAUST IN RESTROOMS. INSPECTED CONDENSATE DRAIN LINES. OK FOR SHEET ROCK. |