Permit: T02CM04035

Parcel: 134090010

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T02CM04035

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/13/2003 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*/ NEED TO SEE DUCT SMOKE DETECTOR, UNIT 8. PROVIDE MIN. 1" CLEARANCE FROM INSULATION AND COMBUSTABLES AROUND WATER HEATER VENT. PROVIDE AN EXPLANATION FROM YOUR ENGINEER WHY AC-7 HAS A DUCT SMOKE DETECTOR AND WHY IT IS IN THE SUPPLY DUCT. COMBUSTION AIR DUCTS IN WATER HEATER ROOM MUST BE SEPERATE UNTIL THEY GET TO THE ROOF. LEAVE OUT CEILING TILES IN AREAS TO BE REINSPECTED. WILL CHECK CORRECTIONS ON FINAL.
10/14/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ INSPECTED SUPPLY AND EXHAUST IN RESTROOMS. INSPECTED CONDENSATE DRAIN LINES. OK FOR SHEET ROCK.