Permit: T02CM04034

Parcel: 134090010

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T02CM04034

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/22/2003 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*/ DUCT SMOKE DETECTORS WERE DRAWN IN ERROR ON PLANS. PLANS SHOW DETECTORS IN THE SUPPLY DUCTS. HAVE PLANS REVISED SHOWING PROPER LOCATION. LEAVE OUT A CEILING TILE AT EACH LOCATION.