12/11/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ ALL CORRECTIONS MADE. 2- BACKFLOW [RPB'S] REPORTS. 1-BACTERIA H20 REPORT.
11/26/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000* GAS CARD BY LAST INSP
11/24/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) EXPANSION TANK AT ELECTRIC WATER TO BE SECURED. 2) EXISTING GAS FURNACE TO ADMIN OFFICE PIPING TO BE 6" MIN. ABOVE FINISHED GRADE. ADMIN. 2' FURNACES TO HAVE FLUE VENT 3' ABOVE COOLERS. RETEST PIPING 10 PSI MIN. CALL IN INSP. 3) GAS WH-3 TO HAVE AGA OR CSA APPROVED GAS VALVE. 4) CLEAN OUTS ON BACK TO BACK SINK LAVS. 5) RPB AND CLORINE CERTIFICATIONS.