Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02CM04034
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/11/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ ALL CORRECTIONS MADE. 2- BACKFLOW [RPB'S] REPORTS. 1-BACTERIA H20 REPORT. | |
11/26/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* GAS CARD BY LAST INSP | |
11/24/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) EXPANSION TANK AT ELECTRIC WATER TO BE SECURED. 2) EXISTING GAS FURNACE TO ADMIN OFFICE PIPING TO BE 6" MIN. ABOVE FINISHED GRADE. ADMIN. 2' FURNACES TO HAVE FLUE VENT 3' ABOVE COOLERS. RETEST PIPING 10 PSI MIN. CALL IN INSP. 3) GAS WH-3 TO HAVE AGA OR CSA APPROVED GAS VALVE. 4) CLEAN OUTS ON BACK TO BACK SINK LAVS. 5) RPB AND CLORINE CERTIFICATIONS. |