Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/10/2003 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/1) ALL CORRECTIONS HAVE BEEN MADE. 2) PLEASE PROVIDE CITY APPROVED CHANGES TO PLAN FOR METER LOCATION AND WATER HEATER LOCATION. |