Permit: T02CM04034

Parcel: 134090010

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T02CM04034

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
07/23/2003 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection 0000*
07/22/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/ 1) ALL BUT IN FILL WHERE VEHICLES COME THROUGH
07/21/2003 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection 0999*/ 1) PER GSN PP S101 YOU MAY NOT HAVE A REBAR SPLICE (HORIZONTAL) WITHIN 8' OF A CONTROL JOINT
07/18/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/ 1) TOPPING OUT 232, 234 AND 235, NOT COMPLETE ENOUGH FOR INSPECTION 2) SMALL COLUMNS AT INTERIOR COURT YARD OK TO 4'
07/17/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/ 1) MAIN BLDG. TAPED OUT EXCEPT 234, 235, 232. 2) ROOMS 232, 234, 235 @ 14' AFF. 3) NEED ENGINEER REPORT FOR BOND BEAM @ LINTEL? INSTEAD OF ABOVE LINTEL PER 207/5601 - SEE SPECIAL INSPECTION NOTES DATED 7/9/03.
07/16/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/ 1) GROUTED W/O INSPECTION-NO SPECIAL INSP REPORT ON SITE 2) DAILY FIELD REPORTS ARE REQUIRED TO BE ON SITE, PLEASE TALK TO YOUR SPECIAL INSPECTOR. THE CITY OF TUCSON PERFORMS INSPECTIONS BETWEEN 7:00 AM AND 3:30 PM. IT IS 1:37 PM RIGHT NOW BUT YOUR SITE IS LOCKED
07/15/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/ 1) 13' HIGH NORTH WALLS; NEED VERTS IN OTHER HIGH WALLS
07/14/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/ 1) 4TH LIFT AT ED. BLDG
07/11/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/ 1) 9'-6" AFF-CARE MUST BE TAKEN WHILE GROUTING TO ENSURE 30" ? SPLICE ON VERTICALS
07/10/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/ 1) VARIOUS ELEVATIONS INTERIOR AND WEST WALLS
07/09/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000* TOP OF ALL EXTERIOR 9'-8'' WALL
07/08/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*1) VERTS N CELL BELOW B2 MUST EXTEND TO ??SENT SE DETAIL 208. 2) BOND BEAM REQUIRES 2 EACH #5 BARS AT EACH FACE UNDER BEAM NOT BOND? AT ONE FACE 3) 8' AFF " LOW WALL AREA" AND SW CORNER.
07/07/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/ 1) 9' AFF NSE EXTERIOR 4' AFF INTERIOR EXCEPT MIDDLE SECTION ALONG LINE 12
07/03/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*
07/01/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/ 1) 4' AFF LAUNDRY AND STORAGE AREAS NORTH END
06/30/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*/ 1) 4' EAST WALL AND NORTH RETURN 2) MINIMUM ? SPLICE FOR #5 IS 30", WHEN 2 BARS IN CELL IT'S 39"
06/26/2003 REINFORCED MASONRY PRE-GROUT Partial Approval 1) PRE-GROUT: A) 4' AFF SOUTH EXTERIOR WALL B) 4' AFF WEST RETURN WALL