Permit: T02CM03972

Parcel: 124041020

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/03/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
11/27/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) CANNOT USE SHEETMETAL SCREWS FOR GROUNDING 250-8.
2.) PLEASE DRESS UP CONDUCTORS AT TERMANATIONS.
3.) FILL UNUSED OPENINGS IN FIXTURES
4.) FINISH SEATING ALL CABLES INTO FITTINGS
5.) EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" BETWEEN BOX & DEVICE.
6.) PLEASE STRAP FLEX CONDUIT UNDER COUNTER AND SEAT INTO FITTINGS.