Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM03972
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/03/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
11/27/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1.) CANNOT USE SHEETMETAL SCREWS FOR GROUNDING 250-8. 2.) PLEASE DRESS UP CONDUCTORS AT TERMANATIONS. 3.) FILL UNUSED OPENINGS IN FIXTURES 4.) FINISH SEATING ALL CABLES INTO FITTINGS 5.) EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" BETWEEN BOX & DEVICE. 6.) PLEASE STRAP FLEX CONDUIT UNDER COUNTER AND SEAT INTO FITTINGS. |