Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM03934
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/08/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ OK C OF O. | |
03/04/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ 1) CONCRETE ENCASE EXPOSED PVC AT BLDG. OUTSIDE FEEDER, AT LEAST 2" ABOVE CONDUIT. 2) RE-ROUTE CONDUCTORS INSIDE SERVICE SECTION AND SUPPORT WITH TY-RAPS. 3) UPDATE PANEL SCHEDULE. |