Permit: T02CM03894

Parcel: 12620001A


Addresses:

900 S RANDOLPH WY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/07/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/06/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
10/31/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 2002 NEC 250-24B - REQUIRES A GROUNDED CONDUCTOR SHALL BE RUN TO EACH SERVICE DISCONNECTING MEANS (EVEN THOUGH NOT USED) TO BE SIZED PER 250- 24 B-1 REFERING TO TABLE 250.66. PLAN DOES NOT REFLECT GROUNDED CONDUCTOR BUT INCLUDES GRD (EQUIPMENT).