Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/06/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 10/31/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 2002 NEC 250-24B - REQUIRES A GROUNDED CONDUCTOR SHALL BE RUN TO EACH SERVICE DISCONNECTING MEANS (EVEN THOUGH NOT USED) TO BE SIZED PER 250- 24 B-1 REFERING TO TABLE 250.66. PLAN DOES NOT REFLECT GROUNDED CONDUCTOR BUT INCLUDES GRD (EQUIPMENT). |