Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 10/20/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* 1)1) NEED CLARIFICATION. IS IT THE INTENT OF THE ENGINEER TO ALLOW THE USEAGE OF STEEL REINFORCED SEALTITE FOR THE SERVICE ENTRY CONDUIT. 2) NEED GRND. BUSH & BOND JUMPERS THROUGHOUT ( WHERE NO MYERS TYPE HUB) 3) CHANGE GREEN GROUND TO WHITE NEUTRAL AND HAVE FULL SIZE NEUTRAL ( UNLESS APPROVED CALCS).4) EXCEEDING 10' TAP RULE, RECALL. 5) NEED NEUTRAL RUN TO TOP. |
| 10/03/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ ALL UNDERGROUND TO BE EXPOSED. |
| 10/02/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0920$ |
| 10/01/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0920*/ 1) LEFT MESSAGE ON IVR FOR RECALL TO LEAVE TILE. NUMBER AND OR MENGE OR TO LOCATION AND PLANS |