900 S RANDOLPH WY


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM03894

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/07/2003 ELECTRIC - INTERMEDIATE Approved
10/20/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999* 1)1) NEED CLARIFICATION. IS IT THE INTENT OF THE ENGINEER TO ALLOW THE USEAGE OF STEEL REINFORCED SEALTITE FOR THE SERVICE ENTRY CONDUIT. 2) NEED GRND. BUSH & BOND JUMPERS THROUGHOUT ( WHERE NO MYERS TYPE HUB) 3) CHANGE GREEN GROUND TO WHITE NEUTRAL AND HAVE FULL SIZE NEUTRAL ( UNLESS APPROVED CALCS).4) EXCEEDING 10' TAP RULE, RECALL. 5) NEED NEUTRAL RUN TO TOP.
10/03/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ ALL UNDERGROUND TO BE EXPOSED.
10/02/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920$
10/01/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920*/ 1) LEFT MESSAGE ON IVR FOR RECALL TO LEAVE TILE. NUMBER AND OR MENGE OR TO LOCATION AND PLANS