Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 10/20/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* 1)1) NEED CLARIFICATION. IS IT THE INTENT OF THE ENGINEER TO ALLOW THE USEAGE OF STEEL REINFORCED SEALTITE FOR THE SERVICE ENTRY CONDUIT. 2) NEED GRND. BUSH & BOND JUMPERS THROUGHOUT ( WHERE NO MYERS TYPE HUB) 3) CHANGE GREEN GROUND TO WHITE NEUTRAL AND HAVE FULL SIZE NEUTRAL ( UNLESS APPROVED CALCS).4) EXCEEDING 10' TAP RULE, RECALL. 5) NEED NEUTRAL RUN TO TOP. |
| 10/03/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ ALL UNDERGROUND TO BE EXPOSED. |
| 10/02/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0920$ |
| 10/01/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0920*/ 1) LEFT MESSAGE ON IVR FOR RECALL TO LEAVE TILE. NUMBER AND OR MENGE OR TO LOCATION AND PLANS |