Permit: T02CM03894

Parcel: 12620001A


Addresses:

900 S RANDOLPH WY


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T02CM03894

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
11/07/2003 ELECTRIC - UNDERGROUND Approved
10/10/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) FOR AERATA #1 AND #2 APPROVED, SECONDARY APPROVED. ALL CONDUIT INSIDE NEW PUMP STATION TO BE ? TO BE DEEPER AND PROPER COUPLING CONNECTION AND BONDS WITH ELBOWS OR PROPER HEATING. AT EXISTING AEROATA #3 AND SUP RAY 2A
10/09/2003 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*/ OK TO OPEN 40' EACH END, 10' IN CENTER RECALL INSPECTION
10/07/2003 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999$/ PLEASE OPEN ALL CONDUIT TRENCHES AND RE CALL FOR INSPECTION.
10/06/2003 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*/ 1) MUST OPEN ALL TRENCHES