Permit: T02CM03860

Parcel: 12705028A


Addresses:

4761 E 5TH ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
09/18/2002 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) P.O.C. OF NEW BLDG DRAIN TO EXSISTING BLDG. DRAIN IS OK 3.) OK FOR BACKFILL 4.) OVERHEAD WATER DISTRIBUTION IS OK.
09/17/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) MAX TRAP SIZE FOR A LAVATORY IS 1 1/2" THIS MEANS THE STUBB OUT FOR TRAP ARM MUST BE 1 1/2. 2.) RETEST SYSTEM. 3.) CAN NOT USE 3 X 2 SAN TEE ON ITS BACK. THIS FITTING MUST BE A DIRECTIONAL FITTING. 4.) MUST VERIFY THAT PLUMBER HAS A COMMERCIAL PLBG. CONTRACTORS LICENSE @ TIME OF INSPECTION.
09/12/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999* 1.) MUST PROVIDE WATER TEST ON WASTE & VENT SYSTEM ALL THE UP TO ROOF 2.) CAN NOT HAVE A 2" TRAP ARM THEN REDUCE TO 1 1/2" @ STUBB OUT. THIS TRAP ARM MUST BE 1 1/2" FROM BARREL TO STUBB OUT. 3.) RETEST SYSTEM. 4.) WILL REQUIRE A REVISED & APPROVED PLAN SHOWING WET VENT FOR LAVATORY PRIOR TO FINAL INSPECTION.