Permit: T02CM03857

Parcel: 135070620


Addresses:

2323 S MCCONNELL DR


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T02CM03857

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/26/2002 FRAMING Approved IVRS - Inspection 0000*
09/24/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) SUPPORT PEX IN GARAGE CEILING 2) BANG PLATE PLUMBING AT TOP PLATES IN LAUNDRY 3) SUPPORT WIRES ABOVE KITCHEN STOVE/FRIDGE 4) STRAP LAV HORIZONTAL DRAIN IN 1ST FLOOR CEILING-SOUTH WALL 5) TAPE DUCT TEARS IN KITCHEN CEILING AND DINING CEILING AND ABOVE CEILING 6) BANG PLATE WIRES AT KITCHEN SINK 7) CORRECT FIRE BLOCKING IN PASS THROUGH CAVITY 8) NEED DWV TEST 9) CORRECT DUCT CRIMP AT TOP OF STAIRS 10) FAN WIRING IN HALL BATH NEEDS MOUNTING IN BOX 11) FIRE STOP WALL CHASE IN NORTHWEST BED 12) NAIL OFF FHA STRAPS ABOVE MASTER TUB