Permit: T02CM03799

Parcel: 12510070A


Addresses:

3777 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM03799

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/17/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK FINAL
09/30/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) OK 3/4" PVC OUT TO PARKING STRUCTURE 2) OK PULL BOXES
09/26/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
05/27/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 2ND FLOOR: 1) WAITING ON EXTENDER RINGS 2) FINISH OUTSIDE LIGHTS
05/23/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) UNCOVER PANEL LABELS 2) STRAP M/C CABLE IN CABINET 3) TIGHTEN OFFICE FURNITURE CONNECTION 4) APPROVED EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" FROM BOX TO SURFACE IN NON-COMBUSTIBLES 370-20 5) PROTECT SEAL TITE FROM SHARP METAL EDGES 6) TIGHTEN LOOSE SEAL TITE FITTINGS AND PROPERLY SUPPORT AS PER CODE 7) A MAINTENCE RECEPTACLE IS NEEDED WITHIN 25' OF A/C UNITS 8) MAINTAIN WORKING CLEARANCE IN FORNT OF DISCONNECT 9) FINISH WIRING DISCONNECTS
03/05/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TO ONE SIDE AND INSULATE 2-B.
OK TEMP POWER FOR TEST SUBJECT TO BOND AND OTHER INSPECTORS.
METER 201,202,101, BASEMENT 1, ELEVATOR.