Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM03793
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/23/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
06/20/2003 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000* | |
05/09/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*OK TO TILE SEC 4(CHILDRENS) | |
05/05/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* 1.) IDENTIFY ELECTRIC SUPPORT WIRES AS PER 300-11. 2.) MISSING CONDULET "T" COVER. OK TO TILE EXCEPT AS NOTED SECTION 5 ONLY. 2.) MISSING CONDULET "T" COVER OK TO TILE EXCEPT AS NOTED SECTION 5 ONLY. |
|
05/01/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) SUPPORT WIRES IN FIRE RATED CELING TO BE IDENTIFIED 300-11. 2.) SUPPORT CONDUITS AS PER CODE WITHIN 3' OF BOXES. |
|
04/22/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*SUPPORT WIRES NEEDED ON ALL BOXES IN SUSPENDED CEILING FIE ALARMS. OK CEILING CK ON FINAL ROOM 201. | |
02/18/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) ROOM 160 OK | |
02/07/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
02/03/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* OK ROOM 283 & 105. | |
01/30/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) ALL BOXES IN CEILING TO HAVE SUPPORT WIRES. 2.) TIGHTEN LOOSE FITTINGS. 3.) OK LAYIN FIXTURES HALL 118A, ROOM 105,283,104. |
|
01/21/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
12/30/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*OK .U.G. FEEDER FROM PANEL EAST SIDE TO FRONT SITE LTG. 2.) PLUG UNUSED KO'S IN J-BOXES ABOVE CEILING ALSO EXIT & EM LIGHTS IN GRID NEED SIEZMIC. |
|
12/18/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*NOTES OK ABOVE CEILING PHASE ONE HALLWAYS. | |
12/17/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) SUPPORT EMT CONDUIT WITHIN 3' EACH TERMINATION PER NEC. 2.) SUPPORT BOXES TO STRUCTURE. 3.) SUPPORT MC WITHIN 12" AND EVERY 6' PER NEC. EXCEPT 6' FIXTURE WHIPS. 4.) DO NOT SUPPORT CONDUIT TO CONDUIT. 5.) EM LIGHTS MUST BE SECURED TO STRUCTURE. 6.) 2 X 4 GRID FIXTURES MUST HAVE 2 #8 SCREWS THRU GRID. |
|
12/09/2002 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000*1.) ALL NEW FIXTURES WILL REQUIRE SIEMIC TIES TO STURCTURE ON 2 X 4'S TWO REQUIRED ONE AT EACH END. 2.) ALL J-BOX HAVE TO BE MADE UP AND FINISHED, EXISTING J-BOXES HAVE TO BE COVERED. |
|
11/14/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
10/26/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* |