Permit: T02CM03793

Parcel: 11108313B


Addresses:

2502 N DODGE BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T02CM03793

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/23/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
06/20/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*
05/09/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK TO TILE SEC 4(CHILDRENS)
05/05/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
1.) IDENTIFY ELECTRIC SUPPORT WIRES AS PER 300-11.
2.) MISSING CONDULET "T" COVER.
OK TO TILE EXCEPT AS NOTED SECTION 5 ONLY.
2.) MISSING CONDULET "T" COVER
OK TO TILE EXCEPT AS NOTED SECTION 5 ONLY.
05/01/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) SUPPORT WIRES IN FIRE RATED CELING TO BE IDENTIFIED 300-11.
2.) SUPPORT CONDUITS AS PER CODE WITHIN 3' OF BOXES.
04/22/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*SUPPORT WIRES NEEDED ON ALL BOXES IN SUSPENDED CEILING FIE ALARMS. OK CEILING CK ON FINAL ROOM 201.
02/18/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) ROOM 160 OK
02/07/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
02/03/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000* OK ROOM 283 & 105.
01/30/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) ALL BOXES IN CEILING TO HAVE SUPPORT WIRES.
2.) TIGHTEN LOOSE FITTINGS.
3.) OK LAYIN FIXTURES HALL 118A, ROOM 105,283,104.
01/21/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
12/30/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK .U.G. FEEDER FROM PANEL EAST SIDE TO FRONT SITE LTG.
2.) PLUG UNUSED KO'S IN J-BOXES ABOVE CEILING ALSO EXIT & EM LIGHTS IN GRID NEED SIEZMIC.
12/18/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*NOTES OK ABOVE CEILING PHASE ONE HALLWAYS.
12/17/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*1.) SUPPORT EMT CONDUIT WITHIN 3' EACH TERMINATION PER NEC.
2.) SUPPORT BOXES TO STRUCTURE.
3.) SUPPORT MC WITHIN 12" AND EVERY 6' PER NEC.
EXCEPT 6' FIXTURE WHIPS.
4.) DO NOT SUPPORT CONDUIT TO CONDUIT.
5.) EM LIGHTS MUST BE SECURED TO STRUCTURE.
6.) 2 X 4 GRID FIXTURES MUST HAVE 2 #8 SCREWS THRU GRID.
12/09/2002 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*1.) ALL NEW FIXTURES WILL REQUIRE SIEMIC TIES TO STURCTURE ON 2 X 4'S TWO REQUIRED ONE AT EACH END.
2.) ALL J-BOX HAVE TO BE MADE UP AND FINISHED, EXISTING J-BOXES HAVE TO BE COVERED.
11/14/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
10/26/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*