Permit: T02CM03793

Parcel: 11108313B


Addresses:

2502 N DODGE BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/23/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) ATTACHED LETTER FOR LIGHTING IN FILES AT RECORDS
06/20/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) NOT READY, NO ONE ON SITE
05/18/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
04/22/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
03/27/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK ROOMS 164-194,196-198.
03/04/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK LAUNDRY ROOM #254
2.) FILL UNUSED OPENINGS IN PANEL.
02/20/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*AC UNITS SECTION 5 OK
AC UNITS (5) DINING ROOM AREA OK
NOTE NO GFI'S IN YET.
02/18/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) ROOM 160 OK
02/12/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) MAINTAIN ALL WORKING CLEARANCES IN FRONT OF DISONNECTS 2) PROVIDE MAINTENANCE RECEPTACLES ON ROOF, OK A/C'S SEC #3
02/07/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS ROOMS 218-224,227-229,231-233. OK ABOVE CEILING 208A.
OK 3/4" PVL ACCROSS DRIVE NORTH WEST.
01/28/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK FIRE ALARM WIRE WALLS SEC 3,4,&5 ROOMS.
01/27/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALL NM CABLE ROOMS 236-252 SEC 5
140-157 SEC 4
OK WALL FIRE ROOMS 255-272 SEC 5
OK PVC CONDUITS UNDER SLAB CHAPEL.

1.) PROTECT JUNCTION BOX FROM MOISTURER AND CORROSSION.
01/21/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) PLEASE SUPPORT FIRE ALARM CABLE AS PER CODES 760 & 300. OK NM CABLE ROOMS 202-217,255-272. OK CONDUITS TO DIMMING PANELS ROOM 103.
01/14/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*EXISTING NM CABLE ENTERING BOXES WITHOUT CONNECTORS OR PROTECTION. OK WALLS ROOM 113-128.
01/08/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK TEMP C OF O SECTION #2 SUBJECT TO OTHER INSPECTORS.
1.) PROTECT VDV CABLES ENTERING CONDUITS & WIRE MOLD
2.) FINISH PREVIOUS INSPECTION #4,5,6,
01/03/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
01/02/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) GROUNDING ELECTRODE CONDUCTOR FOR POLE BASE TO BE INSTALLED WITH 20' IN EARTH AND STRAIGHT DOWN UNTIL CONTACT.
12/30/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK U.G. FEEDER FROM PANEL EAST SIDE TO FRONT SITE LTG.
2.) PLUG UNUSED K O'S IN J-BOX ES ABOVE CEILING ALSO EXIT & EM LIGHTS IN GRID NEED SIEZMIC.
12/10/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK PARTIAL U.G. CONDUIT UNDER ASPHALT DRIVEWAY AND PARKING, NORTH OF BLD. AT FLOWER STREET.
11/26/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
11/14/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK ROOMS SECTION 2, EAST & WEST ABOVE CEILING OK ROOMS ONLY.
10/26/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS AND HARD LIDS, SEC. #1. EAST, CENTER, WEST, HALLWAYS & ROOMS.