Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM03793
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/23/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*/ 1) ATTACHED LETTER FOR LIGHTING IN FILES AT RECORDS | |
06/20/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NOT READY, NO ONE ON SITE | |
05/18/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
04/22/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
03/27/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK ROOMS 164-194,196-198. | |
03/04/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK LAUNDRY ROOM #254 2.) FILL UNUSED OPENINGS IN PANEL. |
|
02/20/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*AC UNITS SECTION 5 OK AC UNITS (5) DINING ROOM AREA OK NOTE NO GFI'S IN YET. |
|
02/18/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) ROOM 160 OK | |
02/12/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) MAINTAIN ALL WORKING CLEARANCES IN FRONT OF DISONNECTS 2) PROVIDE MAINTENANCE RECEPTACLES ON ROOF, OK A/C'S SEC #3 | |
02/07/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK WALLS ROOMS 218-224,227-229,231-233. OK ABOVE CEILING 208A. OK 3/4" PVL ACCROSS DRIVE NORTH WEST. |
|
01/28/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK FIRE ALARM WIRE WALLS SEC 3,4,&5 ROOMS. | |
01/27/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK WALL NM CABLE ROOMS 236-252 SEC 5 140-157 SEC 4 OK WALL FIRE ROOMS 255-272 SEC 5 OK PVC CONDUITS UNDER SLAB CHAPEL. 1.) PROTECT JUNCTION BOX FROM MOISTURER AND CORROSSION. |
|
01/21/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) PLEASE SUPPORT FIRE ALARM CABLE AS PER CODES 760 & 300. OK NM CABLE ROOMS 202-217,255-272. OK CONDUITS TO DIMMING PANELS ROOM 103. | |
01/14/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*EXISTING NM CABLE ENTERING BOXES WITHOUT CONNECTORS OR PROTECTION. OK WALLS ROOM 113-128. | |
01/08/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK TEMP C OF O SECTION #2 SUBJECT TO OTHER INSPECTORS. 1.) PROTECT VDV CABLES ENTERING CONDUITS & WIRE MOLD 2.) FINISH PREVIOUS INSPECTION #4,5,6, |
|
01/03/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
01/02/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) GROUNDING ELECTRODE CONDUCTOR FOR POLE BASE TO BE INSTALLED WITH 20' IN EARTH AND STRAIGHT DOWN UNTIL CONTACT. | |
12/30/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK U.G. FEEDER FROM PANEL EAST SIDE TO FRONT SITE LTG. 2.) PLUG UNUSED K O'S IN J-BOX ES ABOVE CEILING ALSO EXIT & EM LIGHTS IN GRID NEED SIEZMIC. |
|
12/10/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK PARTIAL U.G. CONDUIT UNDER ASPHALT DRIVEWAY AND PARKING, NORTH OF BLD. AT FLOWER STREET. | |
11/26/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
11/14/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK ROOMS SECTION 2, EAST & WEST ABOVE CEILING OK ROOMS ONLY. | |
10/26/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK WALLS AND HARD LIDS, SEC. #1. EAST, CENTER, WEST, HALLWAYS & ROOMS. |