Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM03775
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
12/09/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) DWV FAILED WATER TEST 2) CHECK FRAMING AT MECHANICAL ROOM 3) MECHANICAL NOT BLOCKED 3 SIDES AT SOUTHWEST BEDROOM AND MECHANICAL ROOM 4) LOOSE RED HEADS THROUGHOUT 5) FIRE BLOCK MISSING AT MASTER BATH 6) NAIL PROTECT DRYER VENT 7) STOPPED INSPECTION, HAVE SUPERVISOR INSPECT HOUSE BEFORE RECALLING | |
12/05/2002 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) VENT BLOCK 2) CHANGE OUT 8D'S IN THA HANGERS TO 10D'S 3) CHECK SOFT WATER LOOP FOR PRESSURE TEST 3) ELECTRIC OUTLET LOOSE 3) WHAT'S THE AMPERAGE OF THE FURNACE IF ELECTRIC IF GAS NEED 4 FLUE | |
12/03/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) CHECK FOR FIRE BLOCKS 2) CHECK FOR LEAKS AT TUBS 3) CHECK MECHANICAL REGISTER BLOCKING |